11. Appendix B
11.1. Standard Function Block Parameters
432
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Function Block
Bit Meaning
BG CS ML PD PID RA
5
Direct
Acting
X
X
6
Balance
Ramp
X
X
X
7 Track
Enable
X X X X X
8 Track
in
Manual
X X X X X
9
Use PV for BKCAL_OUT
X
X
X
10
Act
on
IR
X
X
X
11
Use
percent
for
IN_1
X
X
12
Obey SP limits if Cas or RCas
X
X
X
X
13
No
OUT
limits
in
Manual
X X X X X X
14
Reserved
15
Reserved
CYCLE_SEL
Classification
Simple Variable
Description
A bit string to identify the block execution method selected
for this resource.
FF Data Type
Bit String
Range
Usage
C/Contained
Length
2
Valid Views
VIEW_2
Storage
Static
Remarks
Changing this parameter may be fatal to communication.
CYCLE_TYPE