6. Operation
6.3. Monitoring Fieldbus Functions Through Monitoring Tab
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
273
July 2010
Honeywell
Step Action
7
This completes the procedure.
REFERENCE - INTERNAL
Please refer to
Link Schedule
and
Function block execution schedule
in this
document for additional schedule information.
CheckingCIOM-A FIM redundancy status and initiating manual switchover
You monitor redundant CIOM-A FIM status and initiate a manual switchover through
the Redundancy Module configuration form in Monitoring mode the same as you would
for a redundant Control Processor Module (CPM). The following illustration shows a
typical Summary tab for a Redundancy Module as viewed in Monitoring mode for
reference.