16. Appendix G
16.1. Loading CIOM-A FIM firmware
520
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Step Action
Result
2
Wait a few minutes for the
modules to reach their normal
operating states.
Check the 4-Character LED
display on the CIOM-A FIM.
If the Link number and number of devices
on the Link are sequencing in the CIOM-
A FIM display, the CIOM-A FIM is
operating and contains some version of
firmware. For example:
In this case, go to the next procedure
Checking firmware version.
If
ALIV
appears in the CIOM-A FIM
display, go to the procedure Loading
Personality image.
3
This completes the CIOM-A FIM
firmware status check. Go to the
next appropriate procedure.
Checking firmware version
Considerations
If you are running R210 or greater software, you launch NTools through Configuration
Studio. On the
Configuration Explorer
tab, click the
Control Strategy
icon and click
Maintain control system firmware
selection in the
I/O and Network Maintenance
box. In this case, skip Steps 1 and 2 in the following procedure.
This procedure assumes that the Experion software has been installed and the Experion
Server is running.
Step Action
Result