11. Appendix B
11.1. Standard Function Block Parameters
492
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Classification
Simple Variable
Description
Defines the priority of the alarm generated by clearing the
WRITE_LOCK.
FF Data Type
Unsigned 8
Range
0 to 63
Usage
C/Alert Priority
Length
1
Valid Views
VIEW_4
Storage
Static
Remarks
XD_SCALE
Classification
Record
Description
Defines the high and low scale values, engineering units
code, and number of digits to the right of the decimal point
used with a specified channel value obtained from the
Transducer.
FF Data Type
DS-68
Range
Usage
C/Scaling
Length
11
Valid Views
VIEW_2
Storage
Static
Remarks
The Data type consists of data that describes floating point
values for display purposes. It uses the following four
elements.
1 Engineering Units at 100 percent
2 Engineering Units at 0 percent