5. Configuration
5.5. Loading Components Online
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
205
July 2010
Honeywell
Load order guidelines
Load control strategy components from the Project tab in the following order to avoid
possible load interaction generated error messages.
Order Component
Typical Loaded Icon in
Monitoring Tab
1 CPM/CEE*
2 FIM/LINK
3
Check for Uncommissioned fieldbus
devices and initiate match function, as
applicable
4 Fieldbus
Device
5 IOM*
6
CM or SCM*
*Please refer to the Control Building Guide for more information about loading these
components.