
11. Appendix B
11.1. Standard Function Block Parameters
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
479
July 2010
Honeywell
Description
Defines timeout in milliseconds for computer writes to
function block RCas locations.
FF Data Type
Unsigned 32
Range
Positive
Usage
C/Contained
Length
4
Valid Views
VIEW_2
Storage
Static
Remarks
SHED_ROUT
Classification
Simple Variable
Description
Defines timeout in milliseconds for computer writes to
function block ROut locations.
FF Data Type
Unsigned 32
Range
Positive
Usage
C/Contained
Length
4
Valid Views
VIEW_2
Storage
Static
Remarks
SIMULATE
Classification
Record
Description
Allows the transducer analog input or output to the block to
be manually supplied, when SIMULATE is enabled. When
SIMULATE is disabled, the simulate value and status track
the actual value and status.
Содержание Experion PKS Series A
Страница 241: ...5 Configuration 5 9 Summary R400 Experion PKS Series A Fieldbus Interface Module User s Guide 241 July 2010 Honeywell ...
Страница 242: ......
Страница 559: ......
Страница 560: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...