5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
194
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Step Action
Result
(Please see previous Attention note
about skipped parameters.)
9
Key in >50<. Click the OK button.
Closes the Block Parameters form and
stores the configuration entries.
(Please see previous Attention note
about skipped parameters.)
10
This completes the PID block
configuration for the sample loop. Go to
the next procedure
Configuring AO block
for sample loop
.
Configuring AO block for sample loop
Step Action
Result
1
In CM101 chart, double-click the AO
function block
Opens the AO Block Parameters form
with Name field highlighted.