
11. Appendix B
11.1. Standard Function Block Parameters
450
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Length
1
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is 0
HI_LIM
Classification
Simple Variable
Description
Defines the high alarm limit setting in engineering units.
FF Data Type
Float
Range
PV_SCALE, + infinity
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is + infinity
HI_PRI
Classification
Simple Variable
Description
Defines priority of the high alarm.
FF Data Type
Unsigned 8
Range
0 to 63
Usage
C/Alert Priority
Length
1
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is 0
Содержание Experion PKS Series A
Страница 241: ...5 Configuration 5 9 Summary R400 Experion PKS Series A Fieldbus Interface Module User s Guide 241 July 2010 Honeywell ...
Страница 242: ......
Страница 559: ......
Страница 560: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...