11. Appendix B
11.1. Standard Function Block Parameters
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
443
July 2010
Honeywell
Description
Represents the raw value from the field device in percent of
transducer span, with a status reflecting the transducer
condition, before signal characterization (L_TYPE) or
filtering (PV_FTIME).
FF Data Type
DS-65
Range
Usage
C/Contained
Length
5
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
Read Only
The Data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
FIELD_VAL_D
Classification
Record
Description
Represents the raw value of a field device discrete input
with a status reflecting the transducer condition.
FF Data Type
DS-66
Range
Usage
C/Contained
Length
2
Valid Views
VIEW_1, VIEW_3
Storage
Dynamic
Remarks
Read Only
The data type consists of the value and status of discrete
Содержание Experion PKS Series A