5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
154
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Step Action
Result
4
Repeat Step 3 for device LX102.
Device is added to the Assigned Devices
list box with the assign state icon.
TIP
If duplicate address error message appears, go to the next section
Checking device
configuration
for details on changing the device's network node address. It is possible
for device addresses to be set to the same default value of 20.
5
Click Close.
Closes the dialog box.
6
Repeat the procedure to assign other
devices or go to the next section
Checking device configuration
Checking device configuration
Use the following procedure to check the configuration of a selected fieldbus device in
the Project tab. This procedure assumes that the device has been assigned to a Link.