13. Appendix D
13.1. Mode Change Conditions
508
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Mode Parameter - Target Attribute Value
Input Parameters
Status Attributes,
Inputs Values and
Resource States
Out of
Service
(OOS)
Manual
(MAN)
Auto-
matic
(Auto)
Cascade
(CAS)
Remote
Cascade
(RCAS)
Remote
Output
(ROUT)
Target mode is CAS
and cascade input
status is not Good -
Initialization
Acknowledge and
actual mode attribute
last execution was not
CAS
N/A N/A N/A Actual
mode
from last
execution
or AUTO
or MAN
N/A N/A
Status attribute of
primary input
parameter is BAD or
Uncertain with option
to treat Uncertain as
BAD and bypass not
set
OOS MAN MAN MAN MAN ROUT
Status attribute of
back calculation input
parameter is BAD
OOS IMAN IMAN IMAN IMAN IMAN
Status attribute of
back calculation input
parameter Good - fault
state active, local
override, not invited, or
initialization request
OOS IMAN IMAN IMAN IMAN IMAN
Tracking is enabled,
track input active and
track override manual
is Enabled.
OOS LO LO
LO
LO
LO
Tracking is enabled,
initiated and track
override manual is
Disabled.
OOS MAN LO
LO
LO
LO
Fault State is active in
an output function
block
OOS LO LO
LO
LO
LO
If target mode has
changed from OOS to
another mode since
the block was last
executed.
- MAN
or
evaluate
d mode
MAN or
evaluated
mode
MAN or
evaluated
mode
MAN or
evaluate
d mode
MAN or
evaluate
d mode