5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
196
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Step Action
Result
ATTENTION
For this example, we will accept the default values for the other parameters on the
Process tab as well as the remaining tabs. These values are okay for the sample loop.
Please feel free to practice entering data in the other tabs, using the online Help for
support.
4
This completes the AO block
configuration for the sample loop. Go to
the next procedure
Wiring blocks in
CM101 for sample loop.
Wiring blocks in CM101 for sample loop
Step Action
Result
1
In CM101 chart, double-click the
OUT_VALUE pin on the AI_LEVEL block.
Pin is highlighted and cursor shape
changes to cross-hairs
.
2
Move cursor so it is aligned on the P1 pin
for the DATAACQ block and click.
Wire is drawn between the pins, P1 pin is
highlighted, and cursor reverts to its
normal shape.
3
Repeat Steps 1 and 2 to wire these other
pins together. Be sure to add vertices
where required by clicking in the desired
path to the final pin.
DATAACQ_101 PV -> PID_101 PV
PID_101 OP -> AO_FLOW
CAS_IN.VALUE
See the following figure for a view of
completed CM101 with all blocks wired.
4
This completes the wiring of the blocks in
CM101. Close the CM101 chart and click
Yes to save changes. Go to the next
procedure
Adding parameter connections
for sample loop interlocks
.