7. Fieldbus Device Commissioning
7.3. Checking Device
282
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Stage Funtion Completed
Return to Stage 9
18
Is lowest signal level over 150 millivolts?
NO
> Go to Stage
19
YES
> Go to Stage
20
19
Insufficient power for device. Check power supply and link
design.
Return to Stage 9
20
Is there an addressing issue?
NO
> Go to Stage
21
YES
> Go to Stage
22
21
Device should be present. Replace the device.
Return to Stage 9
22
Check if address is in unpolled range, check for too many
devices with temporary address.
References:
Tags, Addresses, and Live List
Return to Stage 9
7.3 Checking
Device
Stage Funtion Completed
23
Does firmware - DD Revision match device revision?
NO
> Go to Stage 24
Yes
> Go to Stage 25
24
Upgrade firmware or import new DD file
References:
Replacing Device Template with a Different One