5. Configuration
5.5. Loading Components Online
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
221
July 2010
Honeywell
Step Action
Result
2
Confirm that checkmarks appear in the
LINK and Device checkboxes listed in the
Load? column.
(If you do not want to load a given
device, just click it to remove the check
mark from its check box.)
Identify what components are to be
loaded.
TIP
A Partial Load selection means that the "contained" or internal block parameters will
not be loaded to the device, which reduces the overall load time. It is generally not
necessary to load these types of parameters, since no connections are made to them.
3
Accept the default Partial Load selection
for the Resource and Transducer blocks
for a device.
Confirm Partial Load for Resource and
Transducer blocks that remain dedicated
to the device.