
5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
164
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Making fieldbus block template and assigning function block to device
The following procedure outlines the steps for making user template for a function block
in the Fieldbus Library in Project, adding the block to an instantiated Control Module in
Project, and assigning the block to a fieldbus device. The following procedure makes and
assigns a fieldbus analog input block template for example purposes only. You can easily
adapt this procedure to apply to another Fieldbus Library block. The illustrations in this
procedure are for example purposes only.
Step Action
Result
1
In Project mode, click Library tab, click +
sign for FIELDBUS, and click AI block
icon.
Selects fieldbus Analog Input (AI) block
in the FIELDBUS Library.
2
Click Templates->Make Template.
Calls up AI Block configuration form.
Содержание Experion PKS Series A
Страница 241: ...5 Configuration 5 9 Summary R400 Experion PKS Series A Fieldbus Interface Module User s Guide 241 July 2010 Honeywell ...
Страница 242: ......
Страница 559: ......
Страница 560: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...