18. Appendix I
18.2. Description
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
545
July 2010
Honeywell
Tab
Parameter Default
Value
Description
Time Distribution
Period
(LMINFREC.TDP)
5000
Determines the minimum
frequency of time distribution on
the local link. Its initial value is
the minimum value required for
the link's time synchronization
class and its range is 5
milliseconds to 55 seconds. The
unit is one millisecond.
LAS DB Status
Distribution Period
(LMINFREC.LDP)
5000
This parameter is used by the
LAS to determine the time
between two successive
distributions of the LAS'
database by means of the LAS
database status SPDUs sent on
the local link. Its range is 100
milliseconds to 55 seconds. The
unit is one millisecond.