11. Appendix B
11.1. Standard Function Block Parameters
456
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Length
16
Valid Views
Storage
Dynamic
Remarks
Read Only
The Data type consists of data that describes floating point
alarms. It uses the following five elements.
1 Unacknowledged
2 Alarm State
3 Time Stamp
4 Subcode
5 Value
LO_LO_LIM
Classification
Simple Variable
Description
Defines the setting for the low low alarm in engineering
units.
FF Data Type
Float
Range
- Infinity, PV_SCALE
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is - Infinity
LO_LO_PRI
Classification
Simple Variable
Description
Represents the priority of the low low alarm.