11. Appendix B
11.1. Standard Function Block Parameters
424
Experion PKS Series A Fieldbus Interface Module User's Guide
R400
Honeywell
July
2010
Remarks
The data type consists of the value and status of discrete
value parameters. It uses the following two elements.
1 Status
2 Value
BKCAL_SEL_1
Classification
Record
Description
The selector output value and status associated with
SEL_1 input that is provided to BKCAL_IN of the block
connected to SEL_1 to prevent reset windup.
FF Data Type
DS-65
Range
Usage
O/Back Calculation Output
Length
5
Valid Views
VIEW_3
Storage
Dynamic
Remarks
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
BKCAL_SEL_2
Classification
Record
Description
The selector output value and status associated with
SEL_2 input that is provided to BKCAL_IN of the block
connected to SEL_2 to prevent reset windup.
FF Data Type
DS-65
Range
Usage
O/Back Calculation Output