6. Operation
6.3. Monitoring Fieldbus Functions Through Monitoring Tab
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
261
July 2010
Honeywell
Step Action
Result
3
Press <Tab> twice.
Moves cursor to the Boot Operational
Function Class
TIP
The FIM is the primary Link Master for both Links. If you designate a device as a
"backup" Link Master, be sure it has the capacity to handle the Link Schedule.
Otherwise, you may have to reset the device as a Basic type and restart it to restore
operation, if the Link Schedule is too large for it to handle.
4
If applicable, click
button in the field
and select BASIC from the dropdown
menu.
Initiates online change value prompt.
5
Click the Yes button to acknowledge the
change.
Functional boot class changes to BASIC.
6
Click the OK button to close the
Parameters form.
Return to Control Builder application.
7
Double-click the Resource block icon
.
Calls up Resource Block Parameters
form.