5. Configuration
5.5. Loading Components Online
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
211
July 2010
Honeywell
Step Action
Result
5
Confirm that CIOM-A FIM icon now
appears in Monitoring tab. Click
plus
sign for CIOM-A FIM icon.
Opens directory and exposes LINK icons.
6
This completes CIOM-A FIM load. Go to
the next section
Matching
uncommissioned device to project device
or vice versa
.
Matching uncommissioned device to project device or vice versa
TIP
If you are running R210 or greater software, the FIM will detect when an
uncommissioned (new) device is added to the link, prepare it for joining the
link, and define the device as an uncommissioned Basic device. In this case,
you can skip the following procedure.
Use the following procedure to initiate the device matching function to conveniently
match uncommissioned fieldbus devices with their counterpart devices in the Project tab
or project devices. It is best to match devices before you download the fieldbus device
from Project to the Link.
Step Action
Result
1
If Link is inactive (blue icon), go to Step
2.
If Link is active (green icon), go to Step 6.
Link must be active to detect
uncomminssioned devices on it.