6. Operation
6.3. Monitoring Fieldbus Functions Through Monitoring Tab
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
257
July 2010
Honeywell
REFERENCE - INTERNAL
Please refer to the
Control Building Guide
sections in
On-Line Monitoring
Using Control Builder
for detailed information:
Setting the CEE Inactive
Setting I/O Active
Setting I/O Inactive
Changing Parameters while Monitoring
Checking/changing fieldbus device functional class
TIP
If you are running R210 or greater software, an online wizard will be launched
when you try to change the functional class of a device. In this case, follow
the instructions in the wizard instead of the steps in the following procedure.
Use the following procedure to check and change, if necessary, the functional class of the
fieldbus device. The illustrations used are for example purposes only and may differ from
the actual forms that appear in your system.
Step Action
Result
1
In Monitoring tab, double-click device
icon.
Opens device configuration Parameters
form.