8. Maintenance, Checkout, and Calibration
8.7. Using Fieldbus Device Simulate Function
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
335
July 2010
Honeywell
Step Action
Result
1
Refer to the vendor documentation
supplied with the fieldbus device to
determine the location of the simulate
activating jumper or switch on the device.
A switch or jumper is usually included in
the device to inhibit accidental activation
of the simulate feature.
2
Position the jumper or switch to its
simulate enable position.
You can now activate the function
through the Monitoring tab in Control
Builder.
3
In Monitoring tab, open the directory for
the fieldbus device icon and double click
the Analog Input function block.
Calls up the Block Parameters form.