17. Appendix H
17.1. Important Functional Considerations
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
537
July 2010
Honeywell
Function Indication
Consideration
Incoming Analog
value with status from
fieldbus device to
Experion function
block
A BAD status from
fieldbus device does
not
force Experion function
block value to NaN.
F
OUNDATION
Fieldbus devices may
show the last good value when the
current value is indicated as BAD via
the status. This is
Not
consistent with
normal Experion system operation.