11. Appendix B
11.1. Standard Function Block Parameters
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
427
July 2010
Honeywell
Storage
Dynamic
Remarks
BLOCK_ERR.DISABLED
Classification
Description
Enables you to disable individual block errors.
FF Data Type
Bitstring
Range
Usage
C/Contained
Length
Valid Views
Dynamic
Storage
Remarks
For the blocks such as AI block configured in Control
Modules, when an inactive block error is disabled and
if the block error turns active, the
Alarm Display
will
not display the alarm and the
Event Summary
will not
display the alarm event. For the devices only blocks
such as, Resource or Transducer blocks, block error
alarm appearance in the
Alarm Display
or
System
Status Display
is affected.
Regardless of disabling, the individual block error
status is displayed on the block’s
Maintenance
tab.
When an active block error is disabled, the
Alarm
Display
or
System Status Display
alarm returns to
normal, and
Event Summary
displays the alarm action
as OK.
In the
Alarm Display
or
System Status Display
,
when you acknowledge block error alarms that have
returned to normal, the alarms disappear and
Event
Summary
displays the acknowledged alarms.
When the disable is removed for an active block error,
the
Alarm Display
or
System Status Display
displays
the alarm as active and
Event Summary
receives the
event for that particular alarm.