11. Appendix B
11.1. Standard Function Block Parameters
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
449
July 2010
Honeywell
Remarks
Read Only
The Data type consists of data that describes floating point
alarms. It uses the following five elements.
1 Unacknowledged
2 Alarm State
3 Time Stamp
4 Subcode
5 Value
HI_HI_LIM
Classification
Simple Variable
Description
Defines the high high alarm limit setting in engineering
units.
FF Data Type
Float
Range
PV_SCALE, + infinity
Usage
C/Contained
Length
4
Valid Views
VIEW_4
Storage
Static
Remarks
Initial value is + infinity
HI_HI_PRI
Classification
Simple Variable
Description
Defines priority of the high high alarm.
FF Data Type
Unsigned 8
Range
0 to 63
Usage
C/Alert Priority