8. Maintenance, Checkout, and Calibration
8.10. FIM Self-Test Diagnostic Codes
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
349
July 2010
Honeywell
If Module Health
LED is . . .
And, 4-Character
Display shows . . .
Then, FIM is . . .
RDY
In its READY state and ready for its Boot
image load.
Solid or Flashing
Green
Alternating link states
as noted in the
following rows.
Operating normally. If solid green, there are
Experion Control Data Access (CDA)
connections to the FIM.
If Link 1 or Link 2
LED is . . .
And, 4-Character
Display shows* . . .
Then, LINK is . . .
Off or Flashing Red
X- - -
Down/offline.
Flashing Green
X - FW
Loading firmware.
Flashing Red
X - FE
Having a firmware load error.
X - CE
Having a communications initialization error.
X - DE
Having a database initialization error.
Flashing Green or
Off
X - CI
Initializing communications with fieldbus
devices.
X - DI
Initializing database.
X - YY
Communicating with fieldbus devices.
*Display alternates between Link 1 and Link 2 in two second intervals. The X is either 1
or 2 for the respective Link and YY equals the number of fieldbus devices present on a
given Link.
8.10 FIM Self-Test Diagnostic Codes
The following table lists the self-test diagnostic codes that the FIM steps through upon
power up. If FIM hangs on a test code during power up, cycle power to reboot the FIM.
If error persists, replace the FIM.
Test Code
Target Device(s)
Failure Modes
Function
T000
Signals start of the selftest.
Display Diagnostics
Содержание Experion PKS Series A
Страница 241: ...5 Configuration 5 9 Summary R400 Experion PKS Series A Fieldbus Interface Module User s Guide 241 July 2010 Honeywell ...
Страница 242: ......
Страница 559: ......