Appendix G Conformity with Standards
Appendix-30
■
Leakage current of EMC-filter built-in type of inverters
An EMC filter uses grounding capacitors for noise suppression which increase leakage current. When using an
EMC-filter built-in type of inverters, therefore, check whether there is no problem with electrical systems.
Three-Phase PDS (Power Drive System) with touch currents
≥
3.5 mA AC or
≥
10 mA DC
As the touch current (leakage current) of inverters with EMC-filter is relatively high, it is of essential importance
to always assure a reliable connection to Protective Earth (PE).
In Table G-3, for the inverter types whose leakage currents are equal to or exceed the critical value of 3.5 mA
AC or 10 mA DC (IEC 61800-5-1), the minimum cross sectional area of the PE-conductor should be:
•
10 mm
2
(Cu-conductors)
•
16 mm
2
(Al-conductors)
An electric shock could occur.
Table G-3 Leakage Current of EMC Filter Built-in Type of Inverters
Power supply voltage
Inverter type
Leakage current (mA)
Three-phase 400V *1)
FRN0002E2E-4
*1
FRN0004E2E-4
*1
FRN0006E2E-4
*1
FRN0007E2E-4
*1
FRN0012E2E-4
*1
FRN0022E2E-4
*1
FRN0029E2E-4
*1
FRN0037E2E-4
*1
FRN0044E2E-4
*1
FRN0059E2E-4
4
FRN0072E2E-4
FRN0085E2E-4
11
FRN0105E2E-4
FRN0139E2E-4
FRN0168E2E-4
5
FRN0203E2E-4
FRN0290E2E-4
FRN0361E2E-4
FRN0415E2E-4
FRN0520E2E-4
FRN0590E2E-4
Single-phase 200V *2)
FRN0001E2E-7
*1
FRN0002E2E-7
*1
FRN0004E2E-7
*1
FRN0006E2E-7
*1
FRN0010E2E-7
*1
FRN0012E2E-7
*1
*1) Calculated based on these measuring conditions: 480 V/ 60 Hz, neutral grounding in Y-connection,
interphase voltage unbalance ratio 2%.
*2) Calculated based on these measuring conditions: 240 V/ 60 Hz, one-phase grounding in delta-connection,
interphase voltage unbalance ratio 2%.
Note: A box (
) in the above table replaces GA, GB or C depending on the model.
*1 Please contact Fuji Electric about these models.
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...