4.10 Selecting a Frequency Command Source
4-31
TE
ST
RU
N
P
RO
CE
DU
R
E
Chap 4
4.10.3 Setting up a frequency command with multistep frequency selection
Follow the procedure given below.
(1) Configure the function codes as listed below.
Function code
Name
Function code data
Factory default
E01 to E05
Terminal [X1] to [X5]
Functions
0, 1, 2, 3: Multistep frequency 1 to 15
(0: “SS1”, 1: “SS2”, 2: “SS4”, 3: “SS8”)
0
C05 to C19
Multistep Frequency 1 to 15
0.00 to 500.00 Hz
0.00
Assign signals “SS1”, “SS2”, “SS4” and “SS8” to four out of five digital input terminals [X1] to [X5] by
respective function codes E01 to E05 (data = 0, 1, 2 and 3). Specify multistep frequency commands with C05
to C19.
Turning digital signals “SS1”, “SS2”, “SS4” and “SS8” ON or OFF selectively switches the multistep frequency
commands specified beforehand, as shown in the table below.
Combination of input signals
Selected frequency command
3
“SS8”
2
“SS4”
1
“SS2”
0
“SS1”
OFF
OFF
OFF
ON
C05 (Multistep frequency 1)
Related function codes
C05 to C19
Data setting range:
0.00 to 500.00
OFF
OFF
ON
OFF
C06 (Multistep frequency 2)
OFF
OFF
ON
ON
C07 (Multistep frequency 3)
OFF
ON
OFF
OFF
C08 (Multistep frequency 4)
OFF
ON
OFF
ON
C09 (Multistep frequency 5)
OFF
ON
ON
OFF
C10 (Multistep frequency 6)
OFF
ON
ON
ON
C11 (Multistep frequency 7)
ON
OFF
OFF
OFF
C12 (Multistep frequency 8)
ON
OFF
OFF
ON
C13 (Multistep frequency 9)
ON
OFF
ON
OFF
C14 (Multistep frequency 10)
ON
OFF
ON
ON
C15 (Multistep frequency 11)
ON
ON
OFF
OFF
C16 (Multistep frequency 12)
ON
ON
OFF
ON
C17 (Multistep frequency 13)
ON
ON
ON
OFF
C18 (Multistep frequency 14)
ON
ON
ON
ON
C19 (Multistep frequency 15)
(2) Connect a multistep frequency switch to an X terminal and [CM].
(3) Turn the multistep frequency switch ON (short-circuit). The combination of those input signals selects a
multistep frequency command.
For precautions in wiring, refer to Chapter 2 “INSTALLATION AND WIRING.”
For details on how to modify the function code data, see Chapter 3 “3.4.1 Setting up function codes “Data
Setting:
!f__
through
!o__
”.”
Enabling a multistep frequency command with a multistep frequency switch (ON between X terminal and
[CM]) disables the frequency command 1 specified by F01.
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......