![Fuji Electric FRENIC-Ace series Скачать руководство пользователя страница 174](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846174.webp)
5.2 Function Codes Table
5-4
5.2.2 Function codes table
The table of function codes to be used in FRENIC-Ace is shown below.
■
F codes: Fundamental Functions (Basic function)
Code
Name
Data setting range
C
han
ge
w
hen
ru
nni
ng
D
at
a
co
py
in
g
Factory
Default
Drive control
R
el
at
ed
p
ag
e
V
/f
PG
V/
f
w
/ P
G
Tor
qu
e c
on
tro
l
PM
F00 Data protection
0: No data protection, no digital setting protection
1: With data protection, no digital setting protection
2: No data protection, with digital setting protection
3: With data protection, with digital setting protection
Y Y
0
Y Y Y Y Y 5-45
F01 Frequency setting 1
0: Keypad key operation ( / key)
1: Analog voltage input (Terminal [12])
(from 0 to ±10 VDC)
2: Analog current input (Terminal [C1] (C1 function))
(4 to 20mA DC, 0 to 20mA DC)
3: Analog voltage input (Terminal [12]) + Analog current
input (Terminal [C1] (C1 function))
5: Analog voltage input (Terminal [C1] (V2 function))
(0 to 10 VDC)
7: UP/DOWN control
8: Keypad key operation ( / key)
(With balanceless bumpless)
10: Pattern operation
11: Digital input/output interface card (option) *5
12: Pulse train input
N Y
0
Y Y Y N Y 5-46
F02 Operation method
0: Keypad operation
(rotation direction input: terminal block)
1: External signal (digital input)
2: Keypad operation (forward rotation)
3: Keypad operation (Reverse rotation)
N Y
2
Y Y Y Y Y 5-57
F03 Maximum output frequency 1 25.0 to 500.0 Hz
N Y 200V class
AJKU:60.0
400V class
ACE:50.0
JKU:60.0
Y Y Y Y Y 5-58
F04 Base frequency 1
25.0 to 500.0Hz
N Y 200V class
J:50.0
AUK:60.0
400V class
ACEJ:50.0
UK:60.0
Y Y Y Y Y 5-59
F05 Rated voltage at base
frequency 1
0: AVR disable
(output voltage proportional to power voltage)
80 to 240 V : AVR operation (200V class)
160 to 500V : AVR operation (400V class)
N Y2 200V class
J:200
AK:220
U:230
400V class
EJ:400
A:415
CK:380
U:460
Y Y Y Y Y
F06 Maximum output voltage 1
80 to 240V : AVR operation (200V class)
160 to 500V : AVR operation (400V class)
N Y2
Y Y N Y Y
F07 Acceleration time1
0.00 to 6000 s
* 0.00 is for acceleration and deceleration time cancel
(when performing soft-start and stop externally)
Y Y
6.00
or
20.0
*10
Y Y Y N Y 5-61
F08 Deceleration time1
Y Y
Y Y Y N Y
F09 Torque boost 1
0.0 to 20.0% (% value against base frequency voltage 1)
Y Y
*2
Y Y N N N 5-63
F10 Electronic thermal overload
protection for motor 1
(Select motor characteristics)
1: Enable (For a general-purpose motor with self-cooling
fan)
2: Enable (For an inverter-driven motor (FV) with
separately powered cooling fan)
Y Y
1
Y Y Y Y Y 5-63
F11
(Overload detection level) 0.00 (disable), current value of 1 to 135% of inverter rated
current
(Inverter rated current dependent on F80)
Y Y1
Y2
*3
Y Y Y Y Y
F12
(Thermal time constant) 0.5 to 75.0 min
Y Y
*4
Y Y Y Y Y
Factory default
A (For Asia), C (for China), E (for Europe), U (For USA), J (for Japan), K (for Korea)
indicates quick setup target function code.
*2: Factory defaults are depended on motor capacity. Refer to “5.2.3 Factory default value per applicable electric motor capacitance”.
*3: The motor rated current is automatically set. Refer to “5.2.4 Motor constant”.
*4: 5.0min for inverters of nominal applied motor 22kW or below; 10.0min for those of 30kW or above.
*5: Available at ROM version 0300 or later.
*10: 6.00s for inverters of nominal applied motor 22kW or below; 20.0s for those of 30kW or above.
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......