5.3 Description of Function Codes
5-104
<Operation timing scheme>
•
When the motor speed remains almost the same during coast-to-stop:
•
When the motor speed decreases significantly during coast-to-stop (with the current limiter activated)
•
Secure more than 0.1 second after turning ON the “Switch to commercial power” signal before turning
ON a run command.
•
Secure more than 0.2 second of an overlapping period with both the “Switch to commercial power”
signal and run command being ON.
•
If an alarm has been issued or BX has been ON when the motor drive source is switched from the
commercial power to the inverter, the inverter will not be started at the commercial power frequency
and will remain OFF. After the alarm has been reset or “BX” turned OFF, operation at the frequency of
the commercial power will not be continued, and the inverter will be started at the ordinary starting
frequency.
If you wish to switch the motor drive source from the commercial line to the inverter, be sure to turn “BX”
OFF before the “Switch to commercial power” signal is turned OFF.
•
When switching the motor drive source from the inverter to commercial power, adjust the inverter’s
reference frequency at or slightly higher than that of the commercial power frequency beforehand,
taking into consideration the motor speed down during the coast-to-stop period produced by
switching.
•
Note that when the motor drive source is switched from the inverter to the commercial power, a high
inrush current will be generated, because the phase of the commercial power usually does not match
the motor speed at the switching. Make sure that the power supply and all the peripheral equipment
are capable of withstanding this inrush current.
•
If you have enabled “Restart mode after momentary power failure” (F14 = 3, 4, or 5), keep “BX” ON
during commercial power driven operation to prevent the inverter from restarting after a momentary
power failure.
0.1s min. 0.2s min.
Switch to commercial power “SW50”
Run command “FWD”
Coast to a stop command “BX”
Commercial power
frequency
Motor speed
Inverter output
frequency
Inverter start at commercial
power frequency
Restart mode after momentary
power failure (H13)
Inverter reference
frequency
0.1s min. 0.2s min.
Switch to commercial power “SW50”
Run command “FWD”
Coast to a stop command “BX”
Commercial power
frequency
Motor speed
Inverter output
frequency
Inverter start at commercial
power frequency
Restart mode after momentary
power failure (H13)
Inverter reference
frequency
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......