5.3 Description of Function Codes
5-108
•
When process control is performed by the PID processor integrated in the inverter:
The terminal command Hz/PID (“Cancel PID control”) can switch PID control between enabled (process is to be
controlled by the PID processor) and disabled (process is to be controlled by the manual frequency setting). In
either case, the combination of the “PID control” (J01) or “Selection of normal/inverse operation for frequency
setting 1” (C53) and the terminal command IVS determines the final operation as listed Table 5.3-8 and Table
5.3-9.
Table 5.3-8 When PID control is enabled:
The normal/inverse operation selection for the PID processor output (reference frequency) is as follows.
PID control (Mode selection) (J01)
Terminal command “IVS”
Action
1: Enable (normal operation)
OFF
Normal
ON
Inverse
2: Enable (inverse operation)
OFF
Inverse
ON
Normal
Table 5.3-9 When PID control is disabled:
The normal/inverse operation selection for the manual reference frequency is as follows.
Selection of normal/inverse operation
for frequency setting 1 (C53)
Terminal command “IVS”
Action
0: Normal operation
-
Normal
1: Inverse operation
-
Inverse
When process control is performed by the PID control facility integrated in the inverter, the “IVS” is used
to switch the PID processor output (reference frequency) between normal and inverse, and has no effect
on any normal/inverse operation selection of the manual frequency setting.
(
Function codes J01 to J19, J57 to J62)
■
Interlock – “IL” (Function code data = 22)
In a configuration where a magnetic contactor (MC) is installed in the power output (secondary) circuit of the
inverter, the momentary power failure detection feature provided inside the inverter may not be able to accurately
detect a momentary power failure by itself. Using a digital signal input with the interlock command IL assures the
accurate detection. (
Function code F14)
Terminal command “IL”
Meaning
OFF
No momentary power failure has occurred.
ON
A momentary power failure has occurred. (Restart after a
momentary power failure enabled)
■
Cancel torque control -- “Hz/TRQ” (Function code data = 23)
When torque control is enabled (H18 = 2 or 3), assigning the terminal command “Hz/TRQ” (Cancel torque control)
to any of the general-purpose digital input terminals (data = 23) enables switching between speed control and
torque control.
Cancel torque control signal “Hz/TRQ”
Operation
ON
Cancel torque control (Enable speed control)
OFF
Enable torque control
■
Select link operation (RS-485, BUS option) – “LE” (Function code data = 24)
Turning this terminal command “LE” ON gives priority to frequency commands or run commands received via the
RS-485 communications link (H30) or the fieldbus option (y98). No LE assignment is functionally equivalent to the
“LE” being ON. (
Function codes H30 and y98)
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......