![Fuji Electric FRENIC-Ace series Скачать руководство пользователя страница 754](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846754.webp)
Appendix B Japanese Guideline for Suppressing Harmonics by Customers Receiving High
Voltage or Special High Voltage (General-purpose inverter)
Appendix-14
(2) Values of “Ki (conversion factor)”
Depending on whether an optional ACR (AC reactor) or DCR (DC reactor) is used, apply the appropriate
conversion factor specified in the appendix to the guideline. The values of the conversion factor are listed in Table
B-3.
Table B-3 “Conversion Factors Ki” for General-purpose Inverters Determined by Reactors
Circuit
category
Circuit type
Conversion factor
Ki
Main applications
3
Three-phase bridge
(Capacitor smoothing)
w/o a reactor
K31=3.4
General-purpose inverter
w/- a reactor (ACR)
K32=1.8
Elevator
w/- a reactor (DCR)
K33=1.8
Cold air refrigerating machine
w/- reactors (ACR and DCR)
K34=1.4
Other equipment in general
Some models are equipped with a reactor as a standard accessory.
[ 2 ] Calculation of Harmonic Current
(1) Value of “input fundamental current”
When you calculate the amount of harmonics according to Table 2 in Appendix of the Guideline, you have to
previously know the input fundamental current.
Apply the appropriate value shown in Table B-4 based on the kW rating of the motor, irrespective of the inverter
type or whether a reactor is used.
If the input voltage is different, calculate the input fundamental current in inverse proportion to the
voltage.
Table B-4 “Input Fundamental Currents” of General-purpose Inverters Determined by the Applicable Motor Ratings
Applicable motor rating (kW)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
Input fundamental
current (A)
200V
1.62
2.74
5.50
7.92
13.0
19.1
25.6
36.9
49.8
61.4
400V
0.81
1.37
2.75
3.96
6.50
9.55
12.8
18.5
24.9
30.7
6.6 kV converted value (mA)
49
83
167
240
394
579
776
1121
1509
1860
Applicable motor rating (kW)
22
30
37
45
55
75
90
110
132
160
Input fundamental
current (A)
200V
73.1
98.0
121
147
180
245
293
357
400V
36.6
49.0
60.4
73.5
89.9
123
147
179
216
258
6.6 kV converted value (mA) 2220
2970
73.5
4450
5450
7450
8910
10850 13090 15640
Applicable motor rating (kW)
200
220
250
280
315
355
400
450
500
630
Input fundamental
current (A)
200V
400V
323
355
403
450
506
571
643
723
804
1013
6.6 kV converted value (mA) 19580 21500 24400 27300 30700 34600 39000 43800 48700 61400
(2) Calculation of harmonic current
Usually, calculate the harmonic current according to the Sub-table 3 “Three-phase bridge rectifier with the
smoothing capacitor” in Table 2 of the Guideline’s Appendix. Table B-5 lists the contents of the Sub-table 3.
Table B-5 Generated Harmonic Current (%), 3-phase Bridge Rectifier (Capacitor Smoothing)
Degree
5th
7th
11th
13th
17th
19th
23rd
25th
w/o a reactor
65
41
8.5
7.7
4.3
3.1
2.6
1.8
w/- a reactor (ACR)
38
14.5
7.4
3.4
3.2
1.9
1.7
1.3
w/- a reactor (DCR)
30
13
8.4
5.0
4.7
3.2
3.0
2.2
w/- reactors (ACR and DCR)
28
9.1
7.2
4.1
3.2
2.4
1.6
1.4
ACR:
3%
DCR:
Accumulated energy equal to 0.08 to 0.15 ms (100% load conversion)
Smoothing capacitor: Accumulated energy equal to 15 to 30 ms (100% load conversion)
Load:
100%
100
(%)
current
harmonic
nth
Generated
(A)
current
l
Fundamenta
(A)
current
harmonic
nth
×
=
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......