5.3 Description of Function Codes
5-61
FU
NCT
IO
N
C
O
DE
S
Chap 5
F07, F08
Acceleration time1, Deceleration time 1
Related function codes:
E10, E12, E14 Acceleration time 2, 3, 4
E11, E13, E15 Deceleration time 2, 3, 4
H07 Curve acceleration/deceleration
H56 Deceleration time for forced stop
H54, H55 Acceleration/deceleration time (Jogging)
H57 to H60 Acceleration/deceleration range No. 1, No.2 S-curve range
Acceleration time sets the time taken by the output frequency to reach the maximum output frequency from 0Hz,
and deceleration time sets the time taken by the output frequency to reach 0Hz from the maximum frequency.
•
Data setting range: 0.00 to 6000 (s)
For V/f control
Acceleration time 1
(F07)
Maximum
output
frequency (F03)
Deceleration time 1
(F08)
Starting frequency 1
(F23)
Stop frequency
(F25)
Actual
acceleration time
Actual
deceleration time
■
Acceleration/Deceleration time
Type of
Acceleration/decele
ration time
Function code
Select ACC/DEC time
(
Function code E01 to E05)
Acceleration
time
Deceleration
time
ACC/DEC time 1
F07
F08
“RT2”
“RT1”
Switch by acceleration/deceleration
selection “RT1” “RT2”. (Data = 4 or 5)
When there is no assignment,
acceleration/deceleration time 1 (F07,
F08) are valid.
OFF
OFF
ACC/DEC time 2
E10
E11
OFF
ON
ACC/DEC time 3
E12
E13
ON
OFF
ACC/DEC time 4
E14
E15
ON
ON
At jogging
H54
H55
When Ready for jogging “JOG” is ON, switch to the mode with which
jogging operation is possible. (Data = 10) (
Function code C20)
At Force to stop
-
H56
Turning the Force to stop “STOP” command OFF causes the motor to
decelerate to a stop in accordance with the deceleration time for
forced stop (H56). After the motor stops, the inverter enters the alarm
state with the alarm
er6
displayed. (Data = 30)
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......