3.3 Running Mode
3-12
[ 2 ]
Settings under PID dancer control
To enable the PID dancer control, you need to set the J01 data to “3.”
Under the PID control, the items that can be specified or checked with and
keys are different from those
under the regular frequency control, depending upon the current LED monitor setting. If the LED monitor is set to the
speed monitor (E43 = 0), the item accessible is the primary frequency command; if it is set to any other, the item is
the PID dancer position set point.
Setting the PID dancer position set point with the and
keys
(1) Set the J02 data to “0” (
/ keys on keypad).
(2) Set the LED monitor to something other than the speed monitor (E43=0) when the inverter is in Running
mode. When the keypad is in Programming or Alarm mode, you cannot modify the PID dancer position set
point with the /
key. To enable the PID dancer position set point to be modified with the /
key,
first switch to Running mode.
(3) Press the
/ key to display the PID dancer position set point. The lowest digit and its decimal point blink
on the LED monitor.
(4) To change the PID dancer position set point, press the
/
key again. The command you have specified
will be automatically saved into the inverter’s internal memory as function code J57 data. It is retained even if
you temporarily switch to another PID command source and then go back to the via-keypad PID command.
Furthermore, you can directly configure the command with function code J57.
•
Even if multistep frequency is selected as a PID command (
PID-SS1
or
PID-SS2
= ON), it is possible
to set a PID command using the keypad.
•
When function code J02 is set to any value other than “0,” pressing the /
key displays, on the
LED monitor, the PID command currently selected, but does not allow any change.
•
On the LED monitor, the decimal point of the lowest digit is used to discriminate the PID related data
from the reference command. The decimal point blinks or lights when a PID command or PID
feedback amount is displayed, respectively.
Table 3.3-5 PID Command Manually Set with
/
Key and Requirements
PID control
(Mode selection)
J01
PID control
(Remote command SV)
J02
LED monitor
E43
PID control multistage
command
PID-SS1
,
PID-SS2
With
/
key
3
0
Other than 0
ON or OFF
PID command by keypad
Other than 0
PID command currently
selected
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......