5.3 Description of Function Codes
5-248
5.3.10 U codes (Customizable logic operation)
The customizable logic function allows the user to form a logic or operation circuit for digital/analog input/output
signals, customize those signals arbitrarily, and configure a simple relay sequence inside the inverter.
In the customizable logic, one step (component), depending on the type, is composed of:
(1) Digital 2 inputs, digital 1 logical operation (including timer)
(2) Analog 2 inputs, analog 1 output/digital 1 numerical operation
(3) Analog 1 input, digital 1 input, analog 1 numerical operation, logical operation
and a total of 200 steps can be used to configure a sequence.
■
Modes
Item
Modes
Terminal command
Digital 2 inputs
Analog 2 inputs
Analog 1 input
Digital 1 input
Operation block
Logical operation,
counter, etc.: 13 types
Timer: 5 types
Numerical operation,
comparator, limiter,
etc.: 25 types
Selector, hold, etc.:
12 types
Output signal
Digital 1 output
Analog 1 output/
Digital 1 output
Analog 1 output
Number of steps
200 steps
Customizable logic output signal
10 outputs
Customizable logic processing
time
2 ms (max. 10 steps), 5 ms (max. 50 steps),
10 ms (max. 100 steps), 20ms (max. 200 steps)
Can be selected with a function code.
Customizable logic cancellation
command “CLC”
Allows to stop all the customizable logic operations by assigning “CLC” to
a general-purpose input terminal and turning it ON.
It is used when you want to deactivate the customizable logic temporarily.
Customizable logic timer
cancellation command “CLTC”
Resets the timer, counter and all the previous values used in customizable
logic by assigning “CLTC” to a general-purpose input terminal and turning
it ON. It is used when a customizable logic is changed or if you want to
synchronize it with external sequence.
If you use the customizable logic cancellation command and customizable logic timer cancellation
command, the inverter can unintentionally start because the speed command is unmasked, depending
on the structure of the customizable logic. Be sure to turn OFF the operation command to turn it ON.
A physical injury may result.
A damage may result.
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......