![Fuji Electric FRENIC-Ace series Скачать руководство пользователя страница 188](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846188.webp)
5.2 Function Codes Table
5-18
Code
Name
Data setting range
C
han
ge
w
hen
ru
nni
ng
D
at
a
co
py
in
g
Factory
Default
Drive control
R
el
at
ed
p
ag
e
V
/f
PG
V/
f
w
/ P
G
Tor
qu
e c
on
tro
l
PM
H47 Initial capacitance of DC link
bus capacitor
For adjustment at replacement
(0000 to FFFF in hexadecimal)
Y N
–
Y Y Y Y Y 5-173
H48 Cumulative run time of
capacitors on printed circuit
boards
For adjustment at replacement
Change in cumulative motor run time (Reset is enabled)
(in units of ten hours)
Y N
–
Y Y Y Y Y 5-169
5-173
H49 Starting mode
(Auto search delay time 1)
0.0 to 10.0 s
Y Y
0.0
Y Y Y N Y 5-174
H50 Non-linear V/f 1 (Frequency) 0.0 (Cancel), 0.1 to 500.0 Hz
N Y
0.0
Y Y N N N 5-174
H51
(Voltage) 0 to 240 V:AVR operation ( 200 V class)
0 to 500V:AVR operation ( 400V class)
N Y2
0
Y Y N N N
H52 Non-linear V/f 2 (Frequency) 0.0 (Cancel), 0.1 to 500.0 Hz
N Y
0.0
Y Y N N N
H53
(Voltage) 0 to 240V:AVR operation ( 200V class)
0 to 500V:AVR operation ( 400V class)
N Y2
0
Y Y N N N
H54 Acceleration time
(Jogging) 0.00 to 6000 s
Y Y
6.00
or
20.0
*10
Y Y Y N Y 5-174
H55 Deceleration time (Jogging) 0.00 to 6000 s
Y Y
Y Y Y N Y
H56 Deceleration time for forced
stop
0.00 to 6000 s
Y Y
Y Y Y N Y
H57 1st S-curve acceleration range
(At starting)
0 to 100%
Y Y
10
Y Y Y N Y
H58 2nd S-curve acceleration
range
(At arrival)
0 to 100%
Y Y
10
Y Y Y N Y
H59 1st S-curve deceleration
range
(At starting)
0 to 100%
Y Y
10
Y Y Y N Y
H60 2nd S-curve deceleration
range
(At arrival)
0 to 100%
Y Y
10
Y Y Y N Y
H61 UP/DOWN control
(Initial frequency setting)
0: Initial value is 0.00 Hz
1: Last UP/DOWN command value on releasing the run
command.
N Y
1
Y Y Y N Y 5-174
H63 Low limiter (Mode selection) 0: Limit by F16 (Frequency limiter: Low) and continue to
run
1: If the output frequency lowers below the one limited by
F16 (Frequency limiter: Low), decelerate to stop the
motor.
Y Y
0
Y Y Y N Y 5-174
H64
(Lower limiting frequency) 0.0: Depends on F16 (Frequency limiter, Low)
0.1 to 60.0 Hz
Y Y
1.6
Y Y N N Y 5-174
H65 Non-linear V/f 3 (Frequency) 0.0 (Cancel), 0.1 to 500.0 Hz
N Y
0.0
Y Y N N N 5-174
H66
(Voltage) 0 to 240V: AVR operation ( 200V class)
0 to 500V: AVR operation ( 400V class)
N Y2
0
Y Y N N N
H68 Slip compensation 1
(Operating conditions
selection)
0: Enable during acceleration/deceleration, enable at
base frequency or higher
1: Disable during acceleration/deceleration, enable at
base frequency or higher
2: Enable during acceleration/deceleration, disable at
base frequency or higher
3: Disable during acceleration/deceleration, disable at
base frequency or higher
N Y
0
Y Y N N N 5-174
H69 Anti-regenerative control
(Mode selection)
0: Disable
2: Torque limit control with force-to-stop
(Cancel limit control after three times of deceleration
time has passed)
3: DC link bus voltage control with force-to-stop
(Cancel voltage control after three times of deceleration
time has passed)
4: Torque limit control without force-to-stop
5: DC link bus voltage control without force-to-stop
Y Y
0
Y Y Y N Y 5-175
H70 Overload prevention control
0.00: Follow the deceleration time selected
0.01 to 100.00 Hz/s, 999 (Cancel)
Y Y
999
Y Y Y N Y 5-176
H71 Deceleration characteristics
0: Disable
1: Enable
Y Y
0
Y Y Y N N 5-176
H72 Main power shutdown
detection
(Mode selection)
0: Disable
1: Enable
(Available FRN0088E2
-2
/FRN0059E2
-4
or above)
Y Y
1
Y Y Y Y Y 5-176
H74 Torque limiter *5
(Control target)
0: Torque limit
1: Torque current limit
N Y
1
N N Y Y Y 5-177
H76 Torque limiter (Braking)
(Frequency rising limiter for
braking)
0.0 to 500.0Hz
Y Y
5.0
Y Y N N N 5-177
H77 Service life of DC link bus
capacitor
0 to 8760 (in units of ten hours)
Y N
6132
(ND spec)
Y Y Y Y Y 5-177
*5: Available at ROM version 0300 or later.
*10: 6.00s for inverters of nominal applied motor 22kW or below; 20.0s for those of 30kW or above.
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......