![Fuji Electric FRENIC-Ace series Скачать руководство пользователя страница 607](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846607.webp)
11.2 Currents Flowing Across the Inverter Terminals
11-3
SE
LEC
TI
N
G
P
E
R
IPH
ER
AL
E
Q
U
IPM
E
N
T
Chap 1
1
Table 11.2-1 Currents Flowing across the Inverter Terminals (continued)
HD mode (kW rating motor)
Power supply
voltage
Nominal
applied
motor
(kW)
Inverter type
50Hz, 400V
60Hz, 440V
Braking
resistor
circuit
current
(A)
Input RMS current (A)
DC link
bus
current
(A)
Input RMS current (A)
DC link
bus
current
(A)
DC reactors (DCRs)
DC reactors (DCRs)
w/ DCR
w/o DCR
w/ DCR
w/o DCR
Three-phase
400V/440V
0.75
FRN0002E2■
-4
1.5
2.7
1.8
1.4
2.7
1.7
0.80
1.1
FRN0004E2■
-4
2.1
3.9
2.6
1.9
3.9
2.3
1.1
2.2
FRN
0006E2■
-4
4.2
7.3
5.1
3.8
7.1
4.6
1.8
3.0
FRN
0007E2■
-4
5.8
11.3
7.1
5.3
10.2
6.5
1.8
5.5
FRN0012E2■
-4
10.1
16.8
12.4
9.1
15.7
11.1
2.1
7.5
FRN0022E2
■
-4
14.4
23.2
17.7
13.0
21.0
16.0
3.2
11
FRN0029E2
■
-4
21.1
33.0
25.9
19.0
29.8
23.3
3.1
15
FRN0037E2
■
-4
28.8
43.8
35.3
26.0
39.5
31.9
4.5
18.5
FRN0044E2
■
-4
35.5
52.3
43.5
32.0
47.1
39.2
5.7
22
FRN0059E2
■
-4
42.2
60.6
51.7
38.0
54.6
46.6
7.2
30
FRN0072E2
■
-4
57.0
77.9
69.9
51.4
70.2
63.0
7.7
37
FRN0085E2
■
-4
68.5
94.3
83.9
61.8
85.0
75.7
10
45
FRN0105E2
■
-4
83.2
114
102
75.0
103
91.9
12
55
FRN0139E2
■
-4
102
140
125
91.9
126
113
15
75
FRN0168E2
■
-4
138
-
169
124
-
152
19
90
FRN0203E2
■
-4
164
-
201
148
-
181
24
110
FRN0240E2
■
-4
201
-
246
181
-
222
31
132
FRN0290E2
■
-4
238
-
292
214
-
263
35
160
FRN0361E2
■
-4
286
-
350
258
-
315
42
200
FRN0415E2
■
-4
357
-
437
321
-
394
50
220
FRN0520E2
■
-4
390
-
478
351
-
430
62
250
FRN0590E2
■
-4
443
-
543
399
-
489
71
HD mode (HP rating motor)
Power supply
voltage
Nominal
applied
motor
(HP)
Inverter type
60Hz, 460V
Braking
resistor
circuit
current (A)
Input RMS current (A)
DC link
bus
current
(A)
DC reactors (DCRs)
w/ DCR
w/o DCR
Three-phase
460V
1
FRN0002E2■
-4
1.3
2.7
1.6
0.80
1.5
FRN0004E2■
-4
1.8
3.8
2.2
1.1
3
FRN0006E2■
-4
3.6
7.0
4.4
1.8
4
FRN0007E2■
-4
5.0
9.8
6.1
1.8
7.5
FRN0012E2■
-4
8.9
15.0
10.9
2.1
10
FRN0022E2
■
-4
12.5
20.1
15.3
3.2
15
FRN0029E2
■
-4
18.8
28.6
23.0
3.1
20
FRN0037E2
■
-4
25.1
38.0
30.7
4.5
25
FRN0044E2
■
-4
31.3
45.4
38.3
5.7
30
FRN0059E2
■
-4
36.3
52.6
44.5
7.2
40
FRN0072E2
■
-4
50.2
67.7
61.5
7.7
50
FRN0085E2
■
-4
60.2
82.0
73.7
10
60
FRN0105E2
■
-4
72.7
99.1
89.0
12
75
FRN0139E2
■
-4
89.1
121
109
15
100
FRN0168E2
■
-4
120
-
147
19
125
FRN0203E2
■
-4
143
-
175
24
150
FRN0240
E2■
-4
175
-
214
31
200
FRN0290
E2■
-4
207
-
254
35
250
FRN0361E2■
-4
249
-
305
42
300
FRN0415
E2■
-4
311
-
381
50
350
FRN0520
E2■
-4
340
-
416
62
400
FRN0590E2■
-4
436
-
534
71
Note:
A box (■) in the above table replaces S (Basic type) or E (EMC filter built
-in type) depending on the enclosure.
A box (
) in the above table replaces GA, GB or C depending on the model.
•
Inverter efficiency is calculated using values suitable for each inverter model. The input route mean square
current is calculated based on a power supply capacity of 500 kVA (or 10 times as large as the inverter’s
capacity when the inverter’s capacity exceeds 50 kVA), and a power supply reactance of 5%.
•
The input RMS current listed in the above table will vary in inverse proportion to the power supply voltage, such
as 480 VAC.
•
The braking current is always constant, independent of braking resistor specifications, including standard and
10%ED models.
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......