5.3 Description of Function Codes
5-155
FU
NCT
IO
N
C
O
DE
S
Chap 5
5.3.5 H codes (High performance functions)
H02, H03
Data initialization (Method, Target)
Related function codes: H193,H194 User initialization data (Save, Protect)
Initialize all function code data to the factory defaults. The motor parameters are also initialized.
To change the H02/ H03 data, it is necessary to press the
+
/ keys (simultaneous keying).
H03 data
Function
0
Disable initialization (Settings manually made by the user will be retained.)
1
Initialize all function codes (initialization in accordance with function code H02 setting)
2
Initialize motor 1 parameters in accordance with F42(Drive control selection 1), P02 (Rated
capacity) and P99 (Motor 1 selection)
3
Initialize motor 2 parameters in accordance with A16 (Rated capacity) and A39 (Motor 2 selection)
11
Limited initialization (initialization other than communications function codes): Communication can
be continued after initialization.
12
Limited initialization (initialization of customizable logic function U codes only)
•
When all function codes are initialized, select the initialization method in advance with function code H02.
Selection of H02
Initialization method when 1 is set to H03
Data=0 Fuji standard initial value Initialize all function codes with the Fuji Electric standard factory
defaults.
Data=1 User initial value
Initialize the value with the user setting value saved by H194.
If the user initial value is not saved, initialize it with Fuji standard initial
value (H02=0).
For saving the user initial value, refer to items in function codes H193 and H194.
•
To initialize the motor parameters, set the related function codes as follows.
Step
Item
Data
Function code
1st motor
2nd motor
(1)
Motor selection
Selects the motor type
P99
A39
(2)
Motor (rated capacity) Sets the motor capacity (kW) P02
A16
(3)
Data initialization
Initialize motor parameters
H03 = 2
H03 = 3
Function code data to be initialized
Please refer to the F42 when using PMSM drive (F42=15)
P01, P03, P05 to
P20, P30, P53 to
P56, P60 to P65,
P74,P83 to P90, H46
A15, A17, A20 to
A27, A30 to
A34,A53 to A56
•
Upon completion of the initialization, the H03 data reverts to “0” (factory default).
•
If P02/A16 data is set to a value other than the standard nominal applied motor rating, data initialization with
H03 internally converts the specified value parameters values to the standard nominal applied motor rating.
(See “5.2.4 Motor constant.”)
•
Motor parameters to be initialized are for motors listed below under V/f control. When the base frequency, rated
voltage, and the number of poles are different from those of the listed motors, or when non-Fuji motors or
non-standard motors are used, change the rated current data to that printed on the motor nameplate.
Motor selection
V/f control data
Data = 0 or 4
Fuji standard motors, 8-series
4 poles
200 V/50 Hz, 400 V/50 Hz
Data = 1
HP rating motors
4 poles
230 V/60 Hz, 460 V/60 Hz
When accessing P02 with the keypad, take into account that the P02 data automatically updates data of
P03, P06 through P13, P53 and H46. Also, when accessing function code A16 for the 2nd motor, data of
related function codes for each are automatically updated.
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......