5.3 Description of Function Codes
5-203
FU
NCT
IO
N
C
O
DE
S
Chap 5
■
Display unit (J105)
J105 can select the display units for monitoring PID feedback value with the multi-function keypad (TP-A1-E2C).
Setting “0” selects the factory default unit for the PID feedback value.
J105
Display unit
J105
Display unit
J105
Display unit
0
* (Factory default)
23
L/s (flow)
45
mmHg (pressure)
1
No unit
24
L/min (flow)
46
Psi (pressure)
2
%
25
L/h (flow)
47
mWG (pressure)
4
r/min
40
Pa (pressure)
48
inWG (pressure)
7
kW
41
kPa (pressure)
60
K (temperature)
20
m
3
/s (flow)
42
MPa (pressure)
61
°C (temperature)
21
m
3
/min (flow)
43
mbar (pressure)
62
°F (temperature)
22
m
3
/h (flow)
44
bar (pressure)
80
ppm (density)
* The unit and scale for feedback values are used.
■
Maximum scale/minimum scale (J106, J107)
The PID control values can be converted to a physical quantity that is easy to recognize and displayed accordingly.
Set the maximum scale “PID command value/ display for 100% of a PID feedback value” with J106 and the
minimum scale “PID command value/ display for 0% of a PID feedback value” with J107
The displayed value is determined as follows:
Display value = (PID command value (%)) / 100 * (Max. scale - Min. scale) + Min. scale
•
Data setting range: (Max. scale and min. scale) -999.00 to 0.00 to 9990.00
■
PID multistep command 1 to 3 (J136, J137 and J138)
A PID command value can be given by the PID multistep command and selected by digital inputs programmed with
“PID-SS1” and “PID-SS2” functions. Assign the digital input terminals with “PID-SS1” and “PID-SS2” (
Function
codes E01 to E05, data =171 and 172 respectively).
PID-SS2
PID-SS1
PID multistep command
OFF
OFF
Not selected
OFF
ON
J136: PID multistep command 1 setting range: -999.0 to 0.00 to 9990
ON
OFF
J137: PID multistep command 2 setting range: -999.0 to 0.00 to 9990
ON
ON
J138: PID multistep command 3 setting range: -999.0 to 0.00 to 9990
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......