5.3 Description of Function Codes
5-54
[ 3 ] Frequency setting by digital input signal “UP”/“DOWN” (F01=7)
As frequency setting, UP/DOWN control is selected, and when the terminal command UP or DOWN is turned on
with Run command ON, the output frequency increases or decreases accordingly, within the range from 0 Hz to
the maximum frequency.
To perform frequency setting by UP/DOWN control, it is necessary to set the data of function code F01 to “7” and
assign “UP command [UP], down command [DOWN]” to the digital input terminals.
(
Function code E01 to E05 Data = 17, 18)
Input signal
“UP”
Input signal
“DOWN”
Action
Data = 17
Data = 18
OFF
OFF
The output frequency will be held
ON
OFF
Increase output frequency by currently selected acceleration time
OFF
ON
Decrease output frequency by currently selected deceleration time
ON
ON
The output frequency will be held
■
UP/DOWN control initial value selection
Set initial value of reference frequency when starting UP/DOWN control.
H61 data
Initial value of frequency setting when starting UP/DOWN control.
0
Mode to fix to “0”
When restarting operation (including when the power to the inverter is turned ON), initial
value of setting frequency by UP/DOWN control is cleared with “0”. Increase speed by UP
command.
1
This is the mode to set reference frequency at the previous UP/DOWN control as the initial
value.
The inverter internally holds the output frequency set by UP/DOWN control and starts to
control from the previous operation frequency at the next restart (including powering ON).
At the restart of operation, before the internal frequency reaches the previous output frequency, when
UP/DOWN command is input, output frequency at the point is held internally and UP/DOWN control
starts from that value. Therefore, the previous output frequency data is overwritten and deleted.
Frequency
Run
command
Output frequency
Internally held frequency
UP
command
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......