5.3 Description of Function Codes
5-273
FU
NCT
IO
N
C
O
DE
S
Chap 5
5.3.11 U1 codes (Customizable logic operation)
U101 to U106
Customizable logic
(Operating point 1 (X1, Y1), Operating point 2 (X2, Y2), Operating point 3 (X3, Y3))
By using function block 3001, quadratic function K
A
·x
2
+ K
B
·x + K
C
is calculated relative to the input signal x as
shown in the following diagram, allowing the output to be obtained. Here, K
A
, K
B
, and K
C
are coefficients, and they
can be set with function codes.
X
3
X
2
X
1
Y
3
Y
2
Y
1
P
3
(X
3
,Y
3
)
P
2
(X
2
,Y
2
)
P
1
(X
1
,Y
1
)
0
X
Y
Coefficients K
A
, K
B
, K
C
Coefficients K
A
, K
B
, K
C
for quadratic function K
A
·x
2
+ K
B
·x + K
C
can be set within the following ranges.
Setting range
Coefficient KA
-9.999×105 to 9.999×105
Coefficient KB
-9.999×105 to 9.999×105
Coefficient KC
-9.999×105 to 9.999×105
These coefficients are set using function codes U92 to U97.
Function code
Name
Setting range
U92
Coefficient KA mantissa portion
-9.999 to 9.999
U93
Coefficient KA exponent portion
-5 to 5
U94
Coefficient KB mantissa portion
-9.999 to 9.999
U95
Coefficient KB exponent portion
-5 to 5
U96
Coefficient KC mantissa portion
-9.999 to 9.999
U97
Coefficient KC exponent portion
-5 to 5
Instead of setting the coefficients individually, they can be calculated and set automatically in function codes U92 to
U97, by changing U107 from 0 to 1 after setting the arbitrary three sets of operating point data P
1
(X
1,
Y
1
), P
2
(X
2,
Y
2
), and P
3
(X
3,
Y
3
) from the above diagram in function codes U101 to U106.
Function code
Name
Setting range
U101
Operating point data P1 (X1)
-999.00 to 0.00 to 9990.00
U102
Operating point data P1 (Y1)
999.00 to 0.00 to 9990.00
U103
Operating point data P2 (X2)
999.00 to 0.00 to 9990.00
U104
Operating point data P2 (Y2)
999.00 to 0.00 to 9990.00
U105
Operating point data P3 (X3)
999.00 to 0.00 to 9990.00
U106
Operating point data P3 (Y3)
999.00 to 0.00 to 9990.00
U107
Automatic calculation
0: No calculation, 1: Calculation
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......