![Fuji Electric FRENIC-Ace series Скачать руководство пользователя страница 553](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846553.webp)
9.2 CANopen Communication
9-29
CO
M
M
U
NI
C
AT
IO
N
FUN
CT
IO
N
S
Chap 9
■
1010 / 1011
:
Store / Restore
It is possible to be performed “Store” or “Restore” when the following conditions are satisfied.
1) The inverter is in a stopped state (Gate-off state).
2) The NMT state is in [Pre-operational] stage.
(1) Access
“Store” and “Restore” can be performed by writing the signature shown in the following table to each sub-index.
Index
(HEX)
sub
Description
Signature
1010
1
Store all parameters
“save” (ISO8859/ character)
MSB LSB
65h 76h 61h 73h
2
Store communication parameters
3
Store application parameters
1011
1
Restore default values to all Parameters
“load” (ISO8859/ character)
MSB LSB
64h 61h 6Fh 6Ch
2
Restore default values to communication parameters
3
Restore application parameters
(2) Communication parameters area
No
Index
(HEX)
Sub
Name
Remarks
1
1005
0
COB-ID SYNC
SYN-ID
2
100C
0
Guard time
Guarding error control
3
100D
0
Life time factor
4
1016
1
Consumer Heartbeat time1
Heartbeat error control(consumer)
5
1017
0
Producer Heartbeat time
Heartbeat error control(producer)
6
1029
1
Error beahavior
Comunication error
7
1400
1
COB-ID
1st Receive PDO Communication Parameter
8
2
Transmission Type
9
1401
1
COB-ID
2nd Receive PDO Communication Parameter
10
2
Transmission Type
11
1402
1
COB-ID
3rd Receive PDO Communication Parameter
12
2
Transmission Type
13
1600
0
1st RPDO Number of mapped objects
1st Receive PDO Mapping Parameter
14
1
PDO mapping entry1
15
2
PDO mapping entry2
16
3
PDO mapping entry3
17
4
PDO mapping entry3
18
1601
0
2nd RPDO Number of mapped objects
2nd Receive PDO Mapping Parameter
19
1
PDO mapping entry1
20
2
PDO mapping entry2
21
3
PDO mapping entry3
22
4
PDO mapping entry3
23
1800
1
1st TPDO COB-ID
1st Transmit PDO Communication Parameter
24
2
Transmission Type
25
3
Inhibit Time
26
5
Event Timer
27
1801
1
2nd TPDO COB-ID
2nd Transmit PDO Communication Parameter
28
2
Transmission Type
29
3
Inhibit Time
30
5
Event Timer
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......