![Fuji Electric FRENIC-Ace series Скачать руководство пользователя страница 714](http://html1.mh-extra.com/html/fuji-electric/frenic-ace-series/frenic-ace-series_user-manual_2341846714.webp)
12.3 Common Specifications
12-22
Item
Explanation
Remarks
Contr
ol
Control method
•
V/f control
•
Vector control without speed sensor (Dynamic torque vector)
•
V/f control, with slip compensation
•
V/f control, with slip sensor (PG option
)
•
V/f Control with speed sensor (+Auto Torque Boost)(PG option)
•
Vector control with speed sensor (PG option)
•
Vector control without magnetic pole position sensor
VF
IM-SVC
VF with SC
IMPG-VF
IMPG-ATB
IMPG-VC
PM-SVC
Voltage/frequency
characteristics
•
Possible to set 80 to 240 V / 160 to 500 V at base frequency and at maximum
output frequency.
•
Non-linear V/f setting (3 points):
Free voltage (0 to 240 V / 500 V) and frequency (0 to 500 Hz) can be set.
Torque boost
•
Auto torque boost (For constant torque load)
•
Manual torque boost: Torque boost value can be set between 0.0 and 20.0%
•
Select application load with the function code. (Variable torque load or constant
torque load)
Starting torque
Three phase 400 V class series
•
200% or above, reference frequency 0.5 Hz (HHD-mode inverters of
FRN0072E2■
-4
or below)
150% or above, reference frequency 0.5 Hz (HHD-mode inverters of
FRN0085E2■
-4
or above)
•
120% or above, reference frequency 0.5 Hz (HND/ND mode)
•
150% or above, reference frequency 0.5 Hz (HD mode)
Three phase 200 V class series
•
200% or above, reference frequency 0.5 Hz (HHD-mode inverters of
FRN0069
E2■
-2
or below)
•
120% or above, reference frequency 0.5 Hz (HND-mode inverters of
FRN0069
E2■
-2
or below)
Single phase 200 V class series
•
200% or above, reference frequency 0.5 Hz (HHD-mode inverters of
FRN0011
E2■
-7
or below)
Base frequency 50 Hz, with slip compensation and auto torque boost active
Start/stop operation
Keypad: Start and stop with and
keys (Standard keypad)
Start and stop with / and
keys (Optional multi-function keypad)
External signals (digital inputs):
Forward (Reverse) rotation, stop command (capable of 3-wire operation),
coast-to-stop command, external alarm, alarm reset, etc.
Link operation: Operation through RS-485 (built-in as standard), CANopen (built-in as
standard) or field bus (option) communications link
Switching run command: Remote/local switching, link switching
Frequency setting
Keypad: Using and keys
External potentiometer: Using external frequency command potentiometer.
(External resistor of 1 to 5 k
Ω 1/2
W)
Analog input: 0 to ±10 VDC (±5 VDC)/ 0 to ±100% (terminal [12]),
0 to +10 VDC (+5 VDC)/ 0 to +100% (terminal [12])
4 to 20 mADC/ 0 to +100% (terminal [C1] (C1 function))
4 to 20 mADC/ 0 to ±100% (terminal [C1] (C1 function))
0 to 20 mADC/ 0 to +100% (terminal [C1] (C1 function))
0 to 20 mADC/ 0 to ±100% (terminal [C1] (C1 function))
0 to +10 VDC (+5 VDC)/ 0 to +100% (terminal [C1] (V2 function)),
0 to +10 VDC (+5 VDC)/ 0 to ±100% (terminal [C1] (V2 function))
UP/DOWN operation: Frequency can be increased or decreased while the digital
input signal is ON.
Multistep frequency: Selectable from 16 different frequencies (step 0 to 15)
Pattern operation:
The inverter runs automatically according to the previously
specified run time, rotation direction, acceleration/deceleration
time and reference frequency. Up to 7 stages can be specified.
Link operation: Operation through RS-485 (built-in as standard), CANopen (built-in as
standard) or field bus (option) communications link
Frequency setting: Two types of frequency settings can be switched with an external
signal (digital input). Remote/local switching, link switching
Содержание FRENIC-Ace series
Страница 20: ......
Страница 32: ......
Страница 92: ......
Страница 94: ......
Страница 452: ......
Страница 490: ......
Страница 504: ......
Страница 506: ...8 2 Frequency Setting Section 8 2 8 2 Frequency Setting Section Figure 8 2 1 Frequency Setting Section Block Diagram...
Страница 508: ...8 2 Frequency Setting Section 8 4 Figure 8 2 3 Frequency Setting Section Block Diagram...
Страница 514: ...8 6 Control Section 8 10 3 With speed sensor Figure 8 6 3 V f Control with speed sensor Section Block Diagram...
Страница 520: ...8 6 Control Section 8 16 6 For PMSM Figure 8 6 9 Vector Control For PMSM Section Block Diagram...
Страница 522: ...8 7 FM Output Section 8 18 8 7 FM Output Section Figure 8 7 1 FM Output Section Block Diagram...
Страница 582: ......
Страница 646: ...11 9 Power Regenerative PWM Converters RHC Series 11 42 11 9 5 External dimensions PWM converter Boosting reactor...
Страница 649: ...11 9 Power Regenerative PWM Converters RHC Series 11 45 SELECTING PERIPHERAL EQUIPMENT Chap 11 Charging resistor Fuse...
Страница 664: ...11 15 External Cooling Fan Attachments 11 60...
Страница 690: ......
Страница 692: ......
Страница 720: ......
Страница 738: ......
Страница 787: ......