Setting Parameters
5. Setting Parameters
SD3 Series Instruction Manual
5. Parameters
5. Parameters
No. 70.0
Positioning complete:
Detection criteria - Command Input
Range
Default
Characteristics
0 to 32,767
(See below)
Function
Use
Set the value for a pulse train command input (Speed) to determine Positioning Complete.
Motor Capacity
Default
units
[encoder pulse]
Conversion to Rotational Speed
50 W to 750 W
0
pulse/160 µs
0 r/min
1 kW to 2 kW
0
pulse/200 µs
0 r/min
Velocity
Velocity Command
0
The setting value of No.70.0
Time
Positioning Complete
When positioning is complete, the signal POSIN (positioning complete) will be output to the host
controller.
Normally, "zero" command is the criteria.
No. 71.0
Positioning complete:
Detection delay time
Range
Default
Characteristics
0 to 65,000
(See below)
Function
Use
Specify the delay time to output Positioning Complete signal (POSIN) to the host
controller after Positioning Complete conditions are met.
Motor Capacity
Default
Units
Conversion to Time
50 W to 750 W
20
160 µs
3.2 ms
1 kW to 2 kW
16
200 µs
3.2 ms
Detection delay time
0
Position Deviation
Time
Positioning Complete Range
Positioning Complete
Related To
No.64.0, No.68.0, No.69.0, No.70.0
Содержание SD3 Series
Страница 1: ...R FATEK AUTOMATION CORP Instruction Manual AC SERVO MOTOR and SERVO AMPLIFIER SD3 Series...
Страница 6: ...6 MEMO SD3 Series Instruction Manual...
Страница 52: ...32 MEMO 2 Specifications SD3 Series Instruction Manual...
Страница 92: ...40 MEMO 3 Preparation SD3 Series Instruction Manual...
Страница 292: ...48 MEMO SD3 Series Instruction Manual 6 Operation...
Страница 338: ...46 MEMO SD3 Series Instruction Manual 7 Tuning...
Страница 362: ...24 MEMO 8 Troubleshooting SD3 Series Instruction Manual...
Страница 395: ...MEMO SD3 Series Instruction Manual...
Страница 396: ...R...