Setup & Operation 3. Installation
26
RC620 Rev.8
3.3 Power Supply
3.3.1 Specifications
Ensure that the available power meets following specifications.
Item
Specification
Voltage
AC 200 V to AC 240 V
Phase
Single phase
Frequency
50/60 Hz
Momentary Power
Interrupt
10 msec. Or less
Power Consumption
Max. 2.5 kVA
Actual consumption depends on the model, motion, and load
of the Manipulator.
For approximate power consumption of each model, refer to
the followings.
C3 : 1.2 kVA
G1 : 0.5 kVA
G3 : 1.1 kVA
G6 : 1.5 kVA
G10 : 2.4 kVA
G20 : 2.4 kVA
RS3 : 1.2 kVA
RS4 : 1.4 kVA
Refer to Manipulator manual for Manipulator rated
consumption.
Rated power consumption of X5 varies depending on the
manipulator model. For details, please contact us.
Peak Current
When power is turned ON
: approx. 80 A (2 msec.)
When motor is ON
: approx. 50 A (5 msec.)
Leakage Current
Max. 10 mA
Ground Resistance
100
Ω
or less
Install an earth leakage circuit breaker or a circuit breaker in the AC power cable line at 15 A
or less rated electric current. Both should be a two-pole disconnect type. If you install an
earth leakage circuit breaker, make sure to use an inverter type that does not operate by
induction of a 10 kHz or more leakage current. If you install a circuit breaker, please select
one that will handle the above mentioned “peak current”.
The power receptacle shall be installed near the equipment and shall be easily accessible.
Содержание RC620 CU
Страница 1: ...Rev 8 EM15XC3076F ROBOT CONTROLLER RC620 ...
Страница 2: ...ROBOT CONTROLLER RC620 Rev 8 ...
Страница 17: ...Safety This section contains information for safety of the Robot System ...
Страница 18: ......
Страница 23: ...Setup Operation This section contains information for setup and operation of the Robot Controller ...
Страница 24: ...8 RC620 Rev 8 ...
Страница 137: ...Maintenance This section contains maintenance procedures for the Robot Controller ...
Страница 138: ......