InteliLite 9 Global Guide
88
Events
specification
Protection
type
Description
setpoint.
Analog Input 3 Wrn
WRN
Value measured on analog input 3 is </> than
setpoint.
Analog Input 3 Sd
SD
Value measured on analog input 3 is </> than
setpoint.
Wrn Battery Voltage
WRN
Battery voltage is out of limits given by
and
Battery Overvoltage (page 188)
setpoints.
Binary input
Configurable Warning/BOC/Shutdown alarms on the binary inputs.
Sd Battery Flat
SD
If the controller switches off during starting sequence (
output is active) it doesn’t try to start again and activates
this protection (controller assumes bad battery condition).
Sd Start Fail
SD
Gen-set start failed. All crank attempts were tried without success.
Parameters Fail
NONE
Wrong check-sum of parameters. Happens typically after
downloading new firmware or changing of the parameter. The
controller stays in INIT mode. Check all parameters, change value of
at least one parameter.
Sd Gen Lx >V
BOC Gen Lx <V
(where x=1,2,3)
SD
BOC
The generator voltage is out of limits given by Gen <V BOC and Gen
>V Sd setpoints.
BOC Gen >,
<Frequency
BOC
The generator frequency is out of limits given by
and
setpoints.
BOC Overload
BOC
The load is greater than the value given by
setpoint.
Sd Overspeed
SD
The protection comes active if the speed is greater than
setpoint.
Sd Underspeed
SD
During starting of the engine when the RPM reach the value of
setpoint the starter is switched off and the
speed of the engine can drop under
again.
Then the Underspeed protection becomes active. Protection
evaluation starts 5 seconds after reaching
Emergency Stop
SD
If the input Emergency Stop is opened shutdown is immediately
activated.
GCB Fail
SD
Failure of generator circuit breaker.
MCB Fail
WRN
Failure of mains circuit breaker.
Sd RPM
Measurement Fail
SD
Failure of magnetic pick-up sensor for speed measurement. This
alarm appears, if starter was disengaged for other reason than
overcrossing
(like oil pressure or D+) and at
the end of timer
Maximum Cranking Time (page 160)
there are no
RPMs >
detected.
Wrn Stop Fail
WRN
Gen-set stop failed. See description at Gen-set Operation States
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...