InteliLite 9 Global Guide
243
3Ph4Wire
Grounded Star (Grounded Wye) connection – 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
3x CT (Current Transformer)
Autodetect
High Leg Delta
or
L1 >=100V; L1 <=140V
L2 >=140V
L3 >=100V; L3 <=140V
3PH3Wire or 3Ph4Wire
or
L1 >=100V
L2 >=100V
L3 >=100V
Split Phase
or
L1 >=100V
L2 <= 20V
L3 >=100V
Mono Phase
or
L1 >=100V
L2 <= 20V
L3 <= 20V
Voltage Autodetect
shutdown
Note:
This value is used when any other alternate configuration is not active.
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
100 .. 4000 [RPM]
Default value
1 500 RPM
Alternative config
YES
Step
1 RPM
Comm object
9916
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note:
This value is used when binary input
is active.
Nominal RPM 2