InteliLite 9 Global Guide
330
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
42
Description
The output is intended for control of close coil of generator circuit breaker. The output gives at least 5 second
pulse in the moment the breaker has to be closed.
Image 8.31 GCB ON Coil close command
Image 8.32 Repeated GCB ON coil close command
GCB ON Coil
back to Logical binary outputs alphabetically
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
44
Description
The output is intended for control of undervoltage coil of generator circuit breaker. The output is active the
GCB UV Coil