InteliLite 9 Global Guide
251
3Ph4Wire
Grounded Star (Grounded Wye) connection – 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
3x CT (Current Transformer)
Autodetect
High Leg Delta
or
L1 >=100V; L1 <=140V
L2 >=140V
L3 >=100V; L3 <=140V
3PH3Wire or 3Ph4Wire
or
L1 >=100V
L2 >=100V
L3 >=100V
Split Phase
or
L1 >=100V
L2 <= 20V
L3 >=100V
Mono Phase
or
L1 >=100V
L2 <= 20V
L3 <= 20V
Voltage Autodetect
shutdown
Note:
This value is used when binary input
is active.
Содержание InteliLite 9
Страница 17: ...InteliLite 9 Global Guide 17 Image 3 2 MRS application overview 6 back to Applications overview ...
Страница 41: ...InteliLite 9 Global Guide 41 4 4 12 Example of AMF Wiring ...
Страница 42: ...InteliLite 9 Global Guide 42 4 4 13 Example of MRS Wiring ...
Страница 80: ...InteliLite 9 Global Guide 80 Image 5 11 Flowchart of start of diesel engine ...
Страница 101: ...InteliLite 9 Global Guide 101 5 4 15 Flowchart Image 5 26 Basic flowchart of controller sequences ...
Страница 173: ...InteliLite 9 Global Guide 173 Image 8 7 Idle Time 1 Image 8 8 Idle Time 2 6 back to List of setpoints ...