InteliLite 9 Global Guide
200
Group: AMF settings
Subgroup: AMF Timers
Setpoint group
AMF settings
Related FW
1.1.0
Range [units]
0 .. 6 000 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
8301
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Delay after the mains failure to the start command of the gen-set.
Image 8.13 Emergency Start Delay
Emergency Start Delay
Setpoint group
AMF settings
Related FW
1.1.0
Range [units]
1 .. 3 600 [s]
Default value
20 s
Alternative config
NO
Step
1 s
Comm object
8302
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
This setpoint adjust the delay, how long mains has to be returned after mains fail to start load transfer to
mains.
Mains Return Delay